SIGNAL-20P DESIGN AND OPERATING PRINCIPLES
13
Parameter
name
Description Range
300 ms
Integration
Burglary alarm loop transits into
“Intrusion Alarm” mode when it has
been broken for more than 300 ms
On/Off
10% Devia-
tion Blocking
Burglary alarm loop doesn’t transit
into “Intrusion Alarm” mode when
its resistance has changed more
than 10% within 255 s
On/Off
Relay 1
Control
Relay 2
Control
Relay 3
Control
Relay 4
Control
Relay 5
Control
Assign relay controlling to the
particular loop
On/Off
4.1.1.1 Loop Type
The fundamental configuration parameter identifying the loop control
method and types of detectors to be included is represented by “Loop
Type”. The device supports nine alarm loop types.
The type 1 is the fire smoke loop with double actuation recogni-
tion.
The fire smoke (normally opened) detectors are included into the
alarm loop. The alarm loop statuses can be:
“Armed” – the alarm loop is monitored and its resistance is in normal
range.
“Disarmed” - the alarm loop is not monitored.
“Arm delay” – the arming delay has not yet been elapsed.
“Fire prealarm” – the single detector actuation has been fixed.
“Fire alarm” - actuating more than one detector has been fixed, or af-
ter first detector actuation the Intrusion/Fire delay has expired.
“Loop trbl short” – the alarm loop resistance is less than 100 Ohm.
“Loop trbl open” - the alarm loop resistance is more than 6 KOhm.
“Arm Failed” – the alarm loop was broken when arming.
When detector has actuated the device generates the “Fire Signal”
message and de-energizes the alarm loop for a 3 s. If within 55 seconds
after de-energizing the detector connected to this loop repeats actuation