INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
48
c) Verify the device useful current being not exceeded values pre-
sented by the Table 1.
d) Verify the S2000/S2000M console displaying the occurring events,
such as:
- “RST RS485 LINE” in case of device has been detected
- “DEVICE RESTART” in case of device reset
- “TAMPER ALARM” when device case is opened
6.1.2 Testing in diagnostic mode
Before diagnostic disconnect all relay load circuits!
To run the diagnostic mode open the device cover and press tamper
detector three times for short time (0,1-0,5 s) and once hold for a time at
least 1,5 s. The pause between pressings shall be no more than 0,5 s.
The device being useful, the “Ready” indicator should enter the inter-
rupted quick flashing light mode with the frequency of 2 Hz.
Then all relay outputs shall switch off and loop voltages shall cut out
for 3 s.
After loop voltage having recovered the relays from 1 to 5 in turns
shall switch on and off with the interval of 2 s.
As soon as relay 5 has been switched off the outputs “K” and “З”
shall be supplied for 2 s.
After outputs “K” and “З” having been switched off the device auto-
matically exits out of diagnostic mode and returns into the operating mode.
6.1.3 Alarm loop checking
а) The alarm loop being disconnected (terminal resistor being dis-
connected), measure the first alarm loop voltage. It shall be within the
range from 26,5 to 27,5 V.
b) Connect the terminal resistor 4,7 kОhm to the “ШС1” and read the
ADC value by means of S2000/S2000M as follows:
- Select the menu commands “Request INFO” and "Zone ADC"
gradually
- Enter the device address (the default value is 127) or select the
device descriptor from the list of connected devices with the help of
"t" and "u" keys
- Enter the alarm loop number 1
The value given out shall be within the range from 46 to 50.
c) Repeat the steps from b) item for loops from 2 to 20.