INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
28
№ Program name Program description Initial
status
If ‘Fire prealarm’ switches in interrupted
mode (0,25 s ON and 0,75 s OFF)
If ‘Intrusion alarm’, ‘Entry alarm’ or ‘Arm
failed’ switches in interrupted mode
(0,5 s ON and 0,5 s OFF)
If “Fire trouble” switches in interrupted
mode (0,25 s ON and 1,75 s OFF)
If there is at least one armed loop turns
relay ON
If all loops are disarmed turns relay OFF
10 ‘Alarm output 1’ If all relay assigned loops are armed then
turns ON (close outputs)
else turns OFF (open output)
*
11 ‘ASPT’ If at least two relay assigned loops have
entered the ‘Fire alarm’ status and there
are no broken auxiliary loops turns the
relay ON for a given time
The breaking of an auxiliary loop blocks
switching on
If the auxiliary loop has broken during the
relay control delay then when recovering
the output will be turned ON for a given
time (the auxiliary loop breaking holds
the turning on delay counting)
OFF
12 ‘SIREN’ In case of ‘Fire alarm’ switches in inter-
rupted mode for given time (1,5 s ON
and 0,5 s OFF)
In case of ‘Fire prealarm’ switches in in-
terrupted mode for given time (0,5 s ON
and 1,5 s OFF)
In case of ‘Intrusion alarm’ switches the
relay ON for a given time
OFF
13 ‘Fire output’ In cases of ‘Fire alarm’ or ‘Fire prealarm’
switches ON (closes) output
else OFF (opened) output
*
14
‘Output FAULT’ If there are loops having the statuses
“Fire trouble”, “Disarmed” or “Arm failed”
then switches output OFF (opens)
else ON (closed output)
*