INTRUSION&FIRE ALARM ADDRESSABLE 20-LOOP CONTROL DEVICE
34
doesn’t response to the queries of the net controller which displays the
“FAIL RS485 LINE” message.
If the device has entered the “Device Failed” mode the “Ready” indi-
cator switches in the interrupted mode with high frequency (8Hz).
In case of entering the “Device Failed” mode it is necessary to update
the microcontroller embedded software. To do this:
1. Send the query-by-mail to the NPV BOLID specifying the true device
version.
2. Receive from the NPV BOLID the "ORION_PROG.EXE" loading pro-
gram and embedding software e-file.
3. Connect the device to the personal computer by means of interface
converter PI-GR or S2000-PI manufactured by NPV BOLID.
4. Run the program "ORION_PROG.EXE" and then switch on the de-
vice power supply.
5. Following the loader directives wait until the embedded software up-
date has been finished. After update has completed the device is to
transit the technical readiness mode.
Table 8: “READY” indicator lights
Device operation mode The indicators behavior
Technical readiness mode Light indicator is off
Operating mode
Indicator is lit in case of being connected
to the net controller, or blinks with the 1
Hz frequency otherwise
“Power Failed” mode
Indicator switches in interrupted mode
with 0,125 s ON and 0,875 s OFF
Diagnostic mode Indicator blinks with the 2 Hz frequency
“Device Failed” mode Indicator blinks with the 8 Hz frequency