Orion ISS
www.bolid.com 28
Fire Signal There is an addressable zone with Test status and there are no
zones with Isolated, Trouble, or Fire Prealarm, or Fire Alarm
statuses
Arming Failed At the moment of arming, one of the addressable zones of the
loop has a not Norm status, no other zones having more priority
statuses (said above)
Arming Delay The transient status when after an attempt to arm an addressa-
ble zone the response from the addressable detector is waiting
for, and there are no zones with more priority statuses (said
above)
Dusty Sensor,
Service Required
There is an addressable zone with the Dusty status, all other
zones being in Norm
Disarmed There is a disarmed addressable zone within the loop, all other
zones of the loop being armed
Armed All addressable zones are in norm and armed
If a Fire condition has been detected for an addressable zone of a fire threshold addressable alarm
loop, this loop switches to the Fire Prealarm status. If Fire conditions have been detected for two differ-
ent addressable zones of a loop, the loop switches to the Fire Alarm status. The loop also can switch
from the Fire Prealarm to Fire Alarm status after the programmed Alarm Delay having expired. If the
Alarm Delay is set to zero for this loop, the loop switches to the Fire Alarm status after a single detector
having actuated. If the Alarm Delay is set to 255 (infinite delay), the loop can switch to the Fire Alarm
status only after two detectors having actuated.
If the Signal-10 has no response from an addressable detector within 10 s, the Isolated status is as-
signed to its addressable zone. In such a case the function of breaking the loop to remove the detector
from its mounting base can be avoided and all other detectors in the loop keep their operability. No ter-
mination resistor is included into a fire threshold addressable alarm loop. The loop can be of any topol-
ogy such as a bus, a ring, a star, or any hybrid topology.
While programming the Signal-10, it is possible to specify in advance the addresses of those detectors
which will be included into this threshold addressable alarm loop. It is implemented by the Related Ad-
dressable Devices parameter setting. If the matching an addressable zone to a particular alarm loop is
missed, then this zone is not considered when a generalized status of the alarm loop is formed and is
not affected by arming/disarming commands while the loop is armed/disarmed.