Orion ISS
To make sure your Signal-10 device keeps proper operability it must be inspected by a competent
specialist at least on receipt and annually. The inspection algorithm shall include:
Visual checking Signal-10 for contaminations and mechanical damage
Verifying Signal-10 for secure mounting and wire connection conditions
Inspection of Signal-10 operability in accordance with the techniques shown below
The Signal-10 must be tested under the following ambient conditions:
Temperature 25° ± 10°C
Relative humidity 45 ÷ 80 %
Atmospheric pressure 630 ÷ 800 mm Hg
Figure 17 shows the scheme of wiring the Signal-10 in order to inspect its operability. The operability
inspection lasts no more than 10 minutes.
NOTE:
Power off the device before connecting and disconnecting wires
SIGNAL-10 OPERABILITY INSPECTION
Inspect the device operability by doing the following:
a) Power-up the device. The device built-in sounder should play the Starting signal.
b) Ensure the S2000/S2000М console or another network controller being in use displays the events
of founding the device with the address of the Signal-10 and the device reset.
c) Measure the device consumed current and ensure its value doesn’t exceed the declared value
(see the Specifications section of this Manual).
TESTING THE SIGNAL-10 IN SELF-DIAGNOSTIC MODE
WARNING:
Before testing the Signal-10 in Self-Diagnostic mode detach its outputs from the execu-
tive circuits if activation of executive devices is inadmissible during inspection
To switch the device to the Self-Diagnostic mode make short–short–short–long pressing on the de-
vice tamper switch.