If a PC is used as the network controller, it is connected to the RS-485 system interface via one of Bolid
manufactured interface converters, namely PI-GR, S2000-PI, USB-RS485, or S2000-USB.
If a communication loss has occurred during generating a message, the event will be stored in the Sig-
nal-10 nonvolatile memory. When the communication is restored, the event will be transmitted to the
network controller with the time and data specified by the internal Signal-10 clock.
The Signal-10 nonvolatile memory is capable of storing up to 512 last events.
Following is the list of the messages due to the alarm loops of the Types 1-11 or the Signal-10 itself
which can be displayed by a S2000М console. Messages displayable by other network controllers
(such as a S2000 console, an ARM Orion Workstation, an ARM Orion Pro Workstation) can slightly
differ from the messages shown below (see the Manual for the network controller being in use).
ARMED The alarm loop is armed
ARM FAILED The loop being armed, the loop resistance was not normal
ARM DELAY The Arming Delay has not yet expired for the loop
DISARMED The alarm loop is disarmed
FIRE SIGNAL A smoke fire detector has actuated within the fire loop
FIRE PREALARM A heat detector has actuated or actuation of a heat detector is confirmed
within the fire loop
FIRE ALARM Two fire detectors have actuated within the fire loop or the Alarm Delay
has been expired
LOOP TRBL OPEN Open failure has occurred in the alarm loop
RELAY TRBL OPEN Open failure has occurred in the relay output load circuit
LOOP TRBL SHORT Short failure has occurred in the alarm loop
RELAY TRBL SHORT Short failure has occurred in the relay output load circuit
RELAY RESTORE The relay output load circuit has been repaired
TAMPER ALARM The enclosure of the device has been opened, or the enclosure of the
detector included into the alarm loop of the Type 5 has been opened
TAMPER RESTORE The enclosure of the device has been closed, or the enclosure of the de-
tector included into the alarm loop of the Type 5 has been closed
TESTING The self-diagnostic process has been started for the device
PROGRAMMING The device has been switched to a hardware key programming mode