ALARM LOOP PROGRAMMING
In order to program alarm loops of the Signal-10, select the Alarm Loops tab of the UProg Configura-
tion Tool. All available parameters are shown placed in a table (see Figure 12).
Figure 12. Alarm Loop Programming
Loop Type Adjusting
The main parameter which must be given for each of the connected alarm loop is the Loop Type,
which is by default set to ‘4’ for all the Signal-10 loops. All available Loop Type values are described
in the Alarm Loop Types section of this Manual.
To define the Loop Type value, double click by left mouse button on the cell which is located at the
intersection of Loop Type string and the column related to a required alarm loop. Then select a proper
value from the drop-down list (see Figure 12).
If you are programming a loop or the Type 12 or a loop of the Type 14 an additional pane will appear
at the right part of the UProg window.
While programming a loop of the Type 12, a Programmable Auxiliary alarm loop, the Additional Prop-
erties pane (see Figure 13) is output at the display in order to program all the statuses and transition
thresholds between them as described in the Programmable Auxiliary Alarm Loop (Type 12) section
of this Manual.