the normal range for more than 15 times Alarm Delay value in seconds. By default this parameter is
off.
Disarmed Loop Monitoring
If this parameter is set on for an alarm loop (by default it is set off for all the device alarm loops), then
breaking of this loop being in the Disarmed status will be transmitted to a network controller.
Fire Loop Requery Prohibition
This parameter disables the function of repeated query (or verification) for statuses of alarm loops of
the Types 1 and 2 when a fire detector has actuated. If the Fire Loop Requery Prohibition is set on,
then a single actuation of a smoke detector will switch the alarm loop to the Fire Prealarm status.
By default this parameter is set off, that is, after a single smoke detector actuation the device gener-
ates a Fire Signal message and queries the loop status once more. If within 55 s the detector actu-
ates repeatedly, the alarm loop switches to the Fire Prealarm status, otherwise it returns to the Armed
status.
300-ms Integration Time
This parameter enables to set the integration time for the intrusion alarm loops (of the Types 4, 5, 7,
11). ‘On’ value (it is the default value) means the integration time of 300 s, while ‘Off’ value means the
integration time of 70 ms. In order to avoid false alarms, turn this parameter off only when it is strictly
necessary.
10% Deviation Blocking
The parameter disables for intrusion alarm loops the analysis of sharp deviations of alarm loop re-
sistance values (more than by 10% of a steady value), however staying within the normal range. It is
advisable to set this parameter on for such alarm loops which involves detectors causing high voltage
ripples (the parameter is set off by default).
Relay 1 Control – Relay 4 Control
These parameters must be set on for those loops which condition altering is to lead to activation of
the relevant relay output.
NOTE: If a relay output is intended to be controlled centrally, by network controller commands,
then this parameter MUST be set off for all the alarm loops of the Signal-10.
By default, the relay 1 is related to conditions of the Signal-10 alarm inputs from the first to the fifth,
while the relay 2 is related to conditions of the Signal-10 alarm inputs from the sixth to the tenth. Out-
puts 3 and 4 (The Siren and the Lamp) are related by default to all alarm loops of the Signal-10.