Orion ISS
www.bolid.com 32
For executive programs #1 #8 (general purpose programs), #11 (ASPT), #12 (Siren), #33 (ASPT-1),
#34 (ASPT-A), #35 (ASPT-A1) in case of breaking an Auxiliary alarm loop (of Type 6) related with an
output, switching this output from other related alarm loops is blocked. If upon the recovering of the
Auxiliary loop the conditions for switching the relay remains then:
for the executive programs with unlimited activation time (#1, #2, #5, #6) as well as pro-
grams #12 (ASPT) and #33 (ASPT-1) the relay output will be switched again, but
for the executive programs #3, #4, #7, #8, #34, #35 the output will NOT be switched
Thus, breaking of an Auxiliary alarm loop blocks an execution of the general purpose programs with
unlimited activation time as well as the programs ASPT and ASPT-1, and cancels the execution of the
general purpose programs with a restricted activation time as well as Siren, ASPT-A, ASPT-A1.
NOTE: Local control of relay outputs is more significant than centralized control. That is, if a re-
lay output is related to an alarm loop status in the device settings then remote control
commands of a network controller over RS-485 interface will be ignored.
Centralized Output Control
To enable centralized control for a Signal-10 relay output:
In alarm loop settings, break an association between the output and any alarm loop of the
device (that is, the Relay … Control parameters for this output must be set OFF for all the
alarm loops of the Signal-10
In output settings, assign this relay output to any Executive Program with a suitable initial
relay on/off condition
In the network controller database, assign the output with relevant Orion system partitions
and give a required executive program along with a proper activation time and activation de-
lay.
Table 5. Executive Programs for Relay Outputs
Program Description
Initial
Condition
0 Remote Control The relay is controlled only remotely Off
1 Switch On
The relay is switched on if there is an Intrusion
Alarm or Fire Alarm
Off
2 Switch Off
The relay is switched off if there is an Intrusion
Alarm or Fire Alarm
On
3 Switch On for a Time
The relay is switched on for a specified time if
there is an Intrusion Alarm or Fire Alarm
Off
4 Switch Off for a Time
The relay is switched off for a specified time if
there is an Intrusion Alarm or Fire Alarm
On
5
Blink From Off
Condition
The relay is switched on/off once per second if
there is an Intrusion Alarm or Fire Alarm
Off